I spent yesterday evening babysitting the…

Fri Feb 6 18:34:31 PST 1998 — I spent yesterday evening babysitting the hunt group in an effort to find out if we had bad equipment or bad phone lines which were causing fast busy signals. We worked with Pacific Bell to isolate an improperly configured line which was causing users to get an error recording or fast busy signal instead of getting online. We’ve fixed it, and things are looking great here. I hope that this signals the end of our string of telco and equipment problems. Here’s a brief summary: Bad PacBell switch setup of series completion hunting was limited to a small number of lines, so 92 ports were unavailable to customers. Fixed January 13th. Bad USR implimentation of DMS custom switch protocol caused caller-ID blocked originators to get a fast busy signal. Fixed February 4th. Bad PacBell switch setup of BRI to PRI hunt group bridging was not allowing users to reach all of our equipment. 92 new ports were unavailable to customers. Fixed February 6th.

Thanks for standing by us as we worked out these issues! We’re still working on ‘Unable to negotate a compatable set of network protocols’ with the Intelliserver gear, and with some intermittant problems with authentication. -Dane and everyone else!

Our air conditioning upgrade went very well.

Fri Feb 6 18:33:00 PST 1998 — Our air conditioning upgrade went very well. The new unit has more than enough capacity for our current heat load, and is working great. We’ve got some photos of the crane lift, and we’ll work on getting those online.

We’ve had a brief power outage here, and some

Thu Feb 5 11:53:44 PST 1998 — We’ve had a brief power outage here, and some users connections were terminated. We’re working on a new power plant, but until PG&E and the electrical folks are finished, we’ve got five terminal servers and some modems which are not on protected power. The new power plant upgrade gives us lots of room to grow, plus uninterruptable power for all facilities including air conditioning. Speaking of air conditioning, we are working today on an AC upgrade. We’re replacing an aging 3 ton Carrier unit with a new 5 ton Trane. A massive crane was here at 6AM putting it all on the roof, and they’re still working on hooking it all up. We’re keeping cool, so there’s no worries about overheating currently. This upgrade is what caused the power outage. A loose screw on the power panel bus under the new AC units new breaker caused a short circuit which tripped the facility’s main circuit breaker. To make things even more exciting, Trane shipped us a 3 ton unit instead of a 5 ton, and the installation folks didn’t realize this until it was already partially installed. We’ll have the big crane back here tommorow, and we’ll do the whole thing over again with another unit. It’s been an interesting morning. -Dane

We again spent a large amount of time this…

Thu Feb 5 22:17:07 PST 1998 — We again spent a large amount of time this evening returning fast busy (reorder) tones to customers. I’ve opened up a new repair ticket with PacBell, and I think we’ve isolated one small configuration problem which is having a big effect. The details: When the analog hunt group (522-1001) fills up, it’s supposed to forward on to the X2 hunt group (522-1002). When the X2 gear fills up, it’s supposed to forward on to our new PRI gear (522-1003). When the PRI gear was deployed last week, we tested the last X2 number (547-3309) and it did indeed reach the PRI equipment if it was busy. Great! However, we found tonight that when the number before that (547-3308) is busy, users get a reorder tone! It sounds like there is something wrong with the way that 3308 is configured, and Fred at PacBell is working on it right now. We’ll keep you posted. Meanwhile, if you’re frustrated with all the reorder tones, you can dial 522-1003 and you should have no troubles. -Dane

News services were in a deferred posting mode

Thu Feb 5 22:00:08 PST 1998 — News services were in a deferred posting mode for a few hours this evening while we made minor repairs on the spool filesystem. This goes back to the crash we had at 14:47 today. All posts which users make when we’re in a mode like this are injected into the Usenet system as soon as the filesystem are offline, so both posting and reading behaves the way it should. -Dane

About 16 ports in our analog hunt group…

Thu Feb 5 14:55:25 PST 1998 — About 16 ports in our analog hunt group failed to issue login prompts, and we’ve reset the equipment. This yeilded timeouts during attempts to login for some users between 1pm and 2pm today. There’s just too much odd stuff happening today! -Dane

Our news server crashed and was offline for…

Thu Feb 5 14:47:23 PST 1998 — Our news server crashed and was offline for 10 minutes. There were no filesystem problems, and it’s back online normally now. We’ve had an ongoing problem with occasional crashes with this system, and we’re planning a bios upgrade, as a OS upgrade didn’t fix the trouble. -Dane

We’ve completed X2 deployment on our new USR…

Thu Feb 5 14:44:58 PST 1998 — We’ve completed X2 deployment on our new USR Total Control Enterprise Hub. This equipment serves 522-1003, plus overflow from 522-1002 and 522-1001. Until this deployment was finished, X2 users calling 522-1002 could have ended up on equipment which didn’t support X2. -Dane

PacBell has converted almost all of our…

Wed Feb 4 07:45:51 PST 1998 — PacBell has converted almost all of our digital X2 digital circuits to the new ‘NI-2’ switch protocol. It appears PB overlooked 6 phone lines during the conversion; the other 186 lines were moved without incident. Those 6 lines are still in service, albeit with the old switch protocol — we’re working with PB to complete the transition. -Scott