Author: admin

FlexLink Long Range Intrusive Maintenance

This evening, beginning at 12:01AM, we will be performing intrusive maintenance on equipment serving a portion of our FlexLink Long Range customers in the Santa Rosa area. Affected customers can expect up to 30 minutes of downtime while the work is performed.

-Tim

CLEC Intrusive Maintenance

This evening, beginning at 12:01AM, we will be performing maintenance on equipment serving Fusion and FlexLink customers in Santa Rosa and Petaluma. Affected customers may experience up to 30 minutes of downtime while the work is performed.

-Nathan, Jared, and Tim

Update: The maintenance in both locations has been completed. All affected customers are back online at this time.

FlexLink Long Range Emergency Maintenance

Within the next 30 minutes, we will be performing emergency maintenance on equipment serving a subset of FlexLink Long Range customers in the Santa Rosa area. We expect minimal, if any, impact but there is a chance of up to 5 minutes of downtime for affected customers.

-Tim, Matt, and Robbie

Intrusive CLEC Maintenance

This evening, beginning at 12:01AM, we will be performing maintenance on equipment serving Fusion and FlexLink customers in one portion of San Francisco. Affected customers should only experience 5 minutes of downtime.

-Jared

Emergency CRAC Maintenance

The primary compressor on the B-side of our Core4 CRAC (Computer Room Air Conditioning) system that cools our Santa Rosa datacenter is being taken out of service and electrically swapped with it’s backup compressor.  The primary compressor experienced loss of oil pressure and while it is apparently still functional it has clearly suffered significant internal damage.  Once the primary compressor has been replaced, the backup compressor will be returned to its normal standby operation.

The Core4 CRAC system is 2N redundant so we can loose the entire A or B side of the system and still satisfy the cooling requirements of our datacenter.  Additionally, each primary compressor  on each side  is paired with a backup compressor so should this damaged compressor have actually ceased to function, the backup compressor would have taken over automatically to meet the cooling demand.

The swap was completed in the time it took to draft this notice.  Both sides of the CRAC are currently fully operational.

ATM Customer Aggregation Router Reload

This Thursday, February 24 at 12:01 AM, we will be performing a maintenance reload on our ATM customer aggregation routers. This will result in 5-10 minutes of downtime for Business-T and FRATM customers.

-Jared

Emergency Router Maintenence

At 9:40AM this morning we will be performing an emergency router reload on one of our ATM customer aggregation routers. All connected Business-T and FRATM customers will experience approximately 5 minutes of downtime during the reload.

-Tim and the NOC

Santa Rosa ADSL1 outage

One of the remote terminals serving a large number of customers in Santa Rosa is currently off line resulting in a sync no surf situation. AT&T reports that they have a technician dispatched to repair but we do not have an estimated time of repair.

CLEC Intrusive Maintenance

This evening, beginning at 12:01AM, we will be performing maintenance on equipment serving Fusion and FlexLink customers in Windsor. Affected customers may experience up to 30 minutes of downtime while the work is performed.

-Nathan, Jared, and Tim

Colocation UPS Maintenance

This Friday, starting at 9AM, one of the three UPSes that serves our Santa Rosa datacenter will be undergoing its annual preventative maintenance.  The maintenance is fully scripted with our vendor and no interruption of services are expected.  During the maintenance window our standby genset will be kept running should our PG&E service fail.  -Kelsey and Russ

Update: Fri Feb 18 19:49:15 PST 2011, the schedule maintenance has been completed with some complication.  One of of the bypass contactors jammed preventing the UPS from going back online.  While the contactor eventually actuated and the UPS was brought online, it’s replacement will be scheduled as soon as possible.  -Kelsey and Russ.